Electrical Systems Design Assignment

Assignment Help Electrical Engineering
Reference no: EM133080726

Electrical Systems Design - Level 3 Electrical Installations

Task A - Design project

Building Specification

Building Construction Hotel Extension:
• The building is constructed on a concrete raft with 50 mm screed to the ground floor and chipboard on 100 mm wooded joists for the first floor.
• The walls are thermolite blocks with uPVC cladding, cavity and inner leaf blockwork with plaster finish. Inner wall partitions are blockwork with plaster finish.
• The roof is tiled on a wooden roof truss with waterproof membrane.
• Internal ceilings are plasterboard on the underside of wood joists.

Pool/Café block:
• The building is constructed on a re-enforced concrete base forming the swimming pool and floor with tiled finish throughout the basement areas.
• The first floor is pre-cast concrete on steel supports with 50 mm screed and non-slip vinyl finish.
• The basement walls are re-enforced concrete with internal uPVC cladding.
• The basement ceiling utilises the underside of the concrete floor above.
• The café area walls are wood framed with uPVC outer cladding, thermal insulation and plasterboard inner lining.
• The tiled roof is supported on exposed decorative wooden trusses with internal plasterboard infills on the underside forming an open 'A' roof space with the exception of the building section above the kitchen end of the building which has plasterboard ceilings 2.4 m above ffl forming an enclosed roof space above.
• Inner walls are plasterboard partitions having aluminium frame.

Electrical Installation:
The existing hotel building forms part of a 400 V three-phase TN-C-S system. It has been assessed that there is sufficient capacity for the new works and a new CCU will be installed to supply the new distribution circuits. Ze and PFC have been measured and recorded as 0.09 Ω and 5 kA respectively.
It has been assessed that following installation of the new three-phase distribution circuit to the pool/café block, Zdb and PFC for the new distribution board within the block will be 0.11 Ω and 3.7 kA respectively.

Fire alarm system
This is to be installed by specialist contractors but a 13 A un-switched fused connection unit will be required in the pool/café block to supply a repeater panel.

Heating, ventilation and air-conditioning
This is to be installed by specialist contractors and any supply details are contained in the design specification. Any further considerations can be ignored.

Design Specification Detail

Within the pool/café block, the following design criteria applies-

Ambient temperatures        All basement pool areas                                40 °C

Café open area                                              25 °C

Café Kitchen/servery                                    35 °C

Wiring systems for lighting and small power (see additional information below for specific circuits)

All basement pool areas                                PVC surface conduit with 90 °C thermosetting single-core non- sheathed cables

Café open area                                             PVC surface conduit with 70 °C thermoplastic single-core non- sheathed cables

Café Kitchen/servery                                    PVC surface conduit with 70 °C thermoplastic single-core non- sheathed cables

Grouping of circuits for lighting and small power (see additional information below for specific circuits)

All basement pool areas                                Each circuit will be grouped with no more than 2 other circuits

Café open area                                              Each circuit will be grouped with no more than 1 other circuit

Café Kitchen/servery                                    Each circuit will be grouped with no more than 3 other circuit

Thermal Insulation              All areas              No thermal insulation affects the wiring systems

Circuit lengths                     All areas            To be estimated from drawing scales. For the purpose of this project, no circuit should exceed approximately 30 m.

Other circuit specific detail

230 V 16 A dishwasher in kitchen                    Supplied by a three core 70 °C thermoplastic SWA cable clipped direct

Servery food holding equipment. This unit requires a 16 A 400 V three-phase and neutral supply.

All pool equipment and sauna equipment. This equipment requires a 32 A 400 V three-phase and neutral supply. All equipment associated will be installed by a specialist from a local supply point in the

Supplied using five core 90 °C thermosetting SWA cable clipped direct

Supplied using five core 90 °C thermosetting SWA cable clipped direct equipment room provided as part of the contract.                                                                                                              

The four fridges within the kitchen area should be supplied by two 16 A single- phase circuits to specifically labelled socket-outlets for each fridge. Additional protection should be omitted for these

Supplied by single-core 70 °C thermoplastic non-sheathed cable in surface PVC conduit circuits.

New summer house by existing pool. A 32 A distribution circuit from the pool/café block will supply this new structure which will have a four-way SP-N distribution board fitted.

Supplied by a three core 70 °C thermoplastic SWA cable clipped direct

Question 1 As part of the electrical contract, the client is considering an electric vehicle charging unit in the car park supplied from the existing TN-C-S supply in the main hotel building. Following a site survey it has been decided to install the EV Charging Equipment as part of a TT earthing arrangement.

Draw a fully labelled circuit diagram illustrating the three-phase 400 V supply system and earthing arrangement from the sub-station transformer through to the charging unit. The diagram should show the total earth fault loop path for the charging unit.

Your diagram does not need to show the complete detail of distribution boards, metering or consumer control equipment although the diagram should, as a minimum, indicate a connection point for each item of equipment.

Question 2 a) Select, using manufacturers' data, suitable luminaires for all parts of the pool/café block with exception of the sauna. Your selection should be based on
• energy efficiency
• environment/external influences
• aesthetics
• Your selection does not need to take into consideration suitable levels of illumination for the purpose of this project or any outdoor lighting.

b) Show, on either electronic or hard copies of the drawing, positions of socket-outlets and fused connection units for the new hotel block giving consideration to the following items of equipment in each room:
• kettle
• TV
• provision for phone charging and/or laptop use
• supply to a 700 W air handling unit for heating/cooling (installed by specialist)
• electric towel rail.

c) Show, on either electronic or hard copies of the drawing, positions of the luminaires selected giving each type a suitable form of identification on a separate key.

d) Show, on either electronic or hard copies of the drawing, how each circuit in the new hotel extension is to be arranged. The arrangement must take into account that a fault in any one room must not affect another room.

e) Show, on either electronic or hard copies of the drawing, any further distribution boards that may be required in the hotel extension.

f) Show, on either electronic or hard copies of the drawing, how each lighting circuit in the new pool/café block is to be arranged including switching.

g) Give each circuit a unique form of identification.

h) Complete the legend on the drawings using recognised symbols and descriptions for each symbol used on the drawings.

Question 3 Select, with the aid of manufacturers' data, a suitable range of circuit protective devices for this contract. Your selection should be based on the following:
• Prospective short circuit currents
• Requirements for additional protection and special locations.

Question 4 This question may be answered using the Table 1 or Table 2. It is strongly recommended that you use pencil when completing the table to allow for recalculation of figures.

Determine, for every final circuit in the café/pool block, each of the following.
a) Design current (Ib)
b) Nominal rating and type of protective device (In)
c) Method of installation reference
d) Rating factors that apply
e) Minimum cross-sectional area of live conductors for current capacity and voltage drop
f) Actual voltage drop.
g) Maximum permissible disconnection time for each circuit as given in BS 7671.
h) Earth fault loop impedance
i) Maximum earth fault loop impedance as stated in BS 7671.

Question 5 Determine, for one of the circuits supplying the fridges, the minimum possible cross sectional area of cpc which will satisfy the requirements disconnection as ADS under earth fault conditions and the adiabatic equation as Regulation 543.1.3 in BS 7671.

Question 6 For this question, use the table below. More copies may be made as necessary.

a) Determine the maximum demand for the pool/café block electrical installation before the application of diversity.

b) Determine the maximum demand for the pool/café block electrical installation following the application of diversity.

Question 7 Explain, with the aid of a diagram, how electric shock protection is provided by one of the shaver points in the hotel extension bathrooms using the Protective Measure: Electrical Separation.

Question 8 List, using the box below, five typical extraneous conductive parts and five typical exposed conductive parts that may be found within this entire complex.

Question 9 Complete the box below relating to earthing and bonding.

Question 10 Complete the box below relating to isolation and switching.

Attachment:- Electrical Systems Design.rar

Reference no: EM133080726

Questions Cloud

How many customers should be treated as strategic accounts : A software company has 1000 B2B customers. About 10% of the customers account for 90% of the revenues. 150% profits come from 5% of the customers.
Pursuit of the green fiber bottle : If Carlsberg had an ownership structure more typical of other companies (in which a majority ownership is not held in perpetuity by an industrial foundation lik
What are the key concepts of financial statements : What are the key concepts of financial statements?
What amount of personnel costs will be allocated : If the number of employees is considered the cost driver, what amount of personnel costs will be allocated to Department A
Electrical Systems Design Assignment : Electrical Systems Design Assignment Help and Solution, Level 3 Electrical Installations - Assessment Writing Service
Pharmaceutical patents and pay-for-delay : Farrel, Joseph, and Chicu, Mark. (2018). "Pharmaceutical Patents and Pay-for-Delay: Actavis (2013)" in John Kwoka and Lawrence White (eds), Antitrust Revolution
Describe what has occurred with the commodity category : Research the overall meat commodity index from an economic standpoint
Calculate expected net value of the wildfire protection : Calculate the expected net value of the wildfire protection program assuming the risks are either uncorrelated or uncorrelate. Explain your choice.
Distribution of the lengths of time listeners : CNAE, an all-news AM station, finds that the distribution of the lengths of time listeners are tuned to the station follows the normal distribution.

Reviews

Write a Review

Electrical Engineering Questions & Answers

  Determine what is the ac machine efficiency

Suppose that the machining operation requires 1 kW, that the tool machine ihas 90 percent efficiency, and that the supply current is 14 A rms with a power factor of 0.8. Find the AC machine efficiency.

  Determine the required valve size in inches and centimeters

The level of water in a tank is to be controlled at 20 m, and the output flow rate is nominally through a control valve, as shown in Figure. Under nominal conditions, determine the required valve size in inches and centimeters.

  Why are rf amplifiers necessary in fm receivers

1. What parameter of the intelligence signal causes or determines the rate of carrier frequency deviation 2. If you are tuned to an FM station at a frequency of 100.1 MHz, show the bandwidth allocation for two adjacent stations.

  Determine the combined costs of two circuits

Design the minimum-cost circuit and compare its cost with combined costs of two circuits that implement f and g separately. Assume that the input variables are available in both uncomplemented and complemented forms.

  The power distribution system

What parallel redundancy does to the power distribution system?

  Find the largest possible number of independant vectors

Find the largest possible number of independant vectors v1=column[1 -1 0 0] v2= column[1 0 -1 0] v3=column[ 1 0 0 -1] v4= column[ 0 1 -1 0] v5= column[0 1 0 -1] v6= coolumn[ 0 0 1 -1] note all are column vectors

  What is the surface area in square millimeters of bearnings

A project manager placed an order for ball bearings for some heavy duty manufacturing machinery. What is the surface area in square millimeters of one of these bearnings if it has a diameter of 0.4 inches

  Design a buffer circuit to measure the voltage on capacitor

Design a buffer circuit to measure the voltage on a small capacitor using a bipolar transistor and a DVM. Design a similar circuitusing a FET transistor. Which is better and why

  Determine the maximum bit rate possible

The dispersion parameter of the fibre is D = 80 ps/(km-nm). The LED optical source has a spectral width of 51 nm. Determine the maximum bit rate possible.

  Which signal travels fast

Which signal travels fast? Analog or digital

  Compute the electrical efficiency of the pv cell

Compute the electrical efficiency of the PV cell. Assume that the irradiance efficiency is 22%, compute the overall efficiency of the PV cell.

  Determine a min-cost sop expression

Determine a min-cost SOP expression f and its cost for the PIT given below using: (a) QM+; (b) Petrick's algorithm. Comment on the difference

Free Assignment Quote

Assured A++ Grade

Get guaranteed satisfaction & time on delivery in every assignment order you paid with us! We ensure premium quality solution document along with free turntin report!

All rights reserved! Copyrights ©2019-2020 ExpertsMind IT Educational Pvt Ltd